Sauter flexotron®800
ventilation
Configuration
P100012082
87
16.10 Free cooling
Free cool active:Yes
Outd. temp activation
22.0°C
Outd. Temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
Free cooling
Start: 0
Stop: 7
Time to block heat output
after
free cooling 60 min
Fan output
when free cooling
SAF: 0 %
EAF: 0 %
Outdoor sensor
placed in intake channel
No
For detailed description, see section 5.1.6 Free cooling.