Sauter flexotron®800
ventilation
Temperature
P100012082
62
10
Temperature
Here you can view all actual and setpoint values for temperature control. The menu is
visible to all users, regardless of log on level. However, to make changes you need at
least Operator authority.
The following menus are available providing that the corresponding input is activated:
Setpoint. Control mode 1: Supply air control.
Outdoortemp.:18.4°C
Supply air temp
Act.: 19.8°C Setp
Setp.: 20.0°C
Submenu: Setpoint
Supply air temp
Setp.: 20.0°C
Setpoint. Control mode 2, 5 and 6: Outdoor compensated supply air control.
Outdoortemp.:18.4°C
Supply air temp
Act.: 19.8°C Setp
Setp.: 20.0°C
Submenu: "Setpoint curve"
In control modes five and six, the setpoint relationship is used when supply air
control is active.
Use the eight breakpoints to generate a "setpoint"/"outdoor temperature"
relationship.
Outdoor comp. setp.
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp. setp.
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
Outdoor comp. setp.
10.0°C = 18.0°C
15.0°C = 18.0°C
In-between-values are calculated using straight lines between breakpoints. Setpoints
for temperatures lower than the lowest breakpoint and higher than the highest
breakpoint are calculated by extending the line between the two last breakpoints at
either end.
Example: At the lower end the setpoint is increasing by 1°C for every 5 °C lowering of
the outdoor temperature. So the setpoint at ---23°C would be 25°C + .6x 1.0°C = 25.6°C.