Sauter flexotron®800
ventilation
Configuration
P100012082
81
UI1
Choose AI or DI sign
AI sign: SAF pressure
DI sign: Not used
After choosing AI or DI signal (the unused alternative must be set to
not active
) there
are submenus with settings. These menus are accessed by pressing RIGHT.
UAI1
Sign: SAF pressure
Raw Value:8.5
Compensation: 0.0
UDI1
NO/NC: NO Signal
Not used
Status: No
To simplify adaptation to external functions, all universal inputs configured as digital
inputs can be set to be either normally open, NO, or normally closed, NC.
The inputs are as standard normally open, i. e. if the input is closed, the function
connected to the input in flexotron®800 is activated.
Be careful when changing the input from NO to NC since some digital functions can be
configured to either NO or NC themselves. For example, you can choose if the Fire
alarm input should be activated when it is closed or opened. Therefore, there is a risk
that the signal is changed twice and the result is the opposite of the desired.
16.1.4
Analogue outputs
Analogue outputs are 0…10 V DC.
AO1
Sign: Y1-Heating
Auto
Value: 0.0 V
Analogue outputs can be set in run mode "Auto", "Manual" or "Off".
16.1.5
Digital outputs
DO1
Signal: SAF 1/1-speed
Auto
Status: On
Digital outputs can be set in run mode "Auto", "Manual-On" or "Manual-Off".