Sauter flexotron®800
ventilation
Commissioning
P100012082
30
At the end of each function description there is a table of the necessary inputs and
outputs to implement the function. At the end of the manual there is a list of all the
analogue and digital inputs and outputs. As you read, mark in the list the inputs and
outputs you will be using for the application you are building. Note that the universal
inputs in RDT828 can, individually, be configured as either analogue or digital inputs.
Display, buttons and LEDs
Read chapter 7 on how to use the front panel buttons to navigate the flexotron®800
menu system.
Access rights
Chapter 8. Learn how to log on to the flexotron® 800.
Configuration
Chapter 16. Configuration.
Connect power to the controller. Using the buttons and menu system, go through the
configuration menus covering the functions you wish to use.
On delivery the units already have the inputs and outputs assigned to various functions.
These can, of course, be changed. In chapter 3
Installation and wiring
there are two
sets of wiring diagrams, one set showing the pre-configured input / output configuration
and one set where you can fill your own configuration choices.
Settings
Chapter 15
Set the control parameters, P-band, I-time for the temperature control.
Set the control parameters for the pressure control if you have pressure- or flow-
controlled fans.
Set the control parameters for the humidity control if activated.
Set the alarm parameters; alarm levels and delay times.
Time settings
Chapter 13
Set the clock and calendar functions.
Setpoints
Chapters 10, 11 and 12:
Set all the setpoints for all active control loops.
Manual/Auto
Chapter 14
Learn to use manual control. Very useful for testing out your system.
Other functions
Chapter 18
Alarm handling etc.