Sauter flexotron®800
ventilation
Settings
P100012082
75
15.2
Control pressure
Pressure control SAF
Pressure control SAF
P-band: 500 Pa
I-time: 60 sec
Min Output: 0 %
Pressure control EAF
Pressure control EAF
P-band: 500 Pa
I-time: 60 sec
Min Output: 0 %
15.3
Control flow
Flow control SAF
Flow control SAF
P-band: 1000 m3/h
I-time: 60 sec
Min Output: 0 %
Flow control EAF
Flow control EAF
P-band: 1000 m3/h
I-time: 60 sec
Min Output: 0 %
15.4
Humidity control
Control humidity
P-band: 100.0 %RH
I-time: 300.0 sec
15.5
Control Extra unit
Control extra
unit
P-band: 33.0 °C
I-time: 100.0 sec
15.6
Alarm settings
Alarm settings
Alarm limits
Alarm delays
Restore alarm