Sauter flexotron®800
ventilation
Configuration
P100012082
106
16.28.10 Automatic restart at power-up
The function
’’Automatic restart at power-up’’ makes it possible to block automatic
restart of the unit at power-up. At power-up, the B-alarm
’’Restart blocked after power
on
’’ is generated. Once this alarm has been acknowledged, the unit will start.
Automatically
restart after
power on:
Yes
16.29 System
16.29.1 Change language
Use this menu to change the display language.
Choose language
English
Note, this menu is also directly accessible by holding the OK-button depressed during
power-up or by pressing right arrow three times when the start display is shown.
The different language files are stored in the application memory and are downloaded
to the work memory. If a flexotron®800 via CASE flexotron® has been reloaded with a
newer program revision than the factory revision, the controller will not allow language
files to be downloaded from the application memory. This is because there is a risk that
the language files are not compatible with the new revision. Therefore, you are limited
to the two languages you have downloaded using CASE flexotron®.
16.29.2 Choose start display, the text normally shown on the display
There are five different to choose from.
Type 1
The text on the first line can be changed using CASE flexotron®.
The second line shows the date and time.
The third line shows the present running status.
The fourth line shows the present temperature setpoint and actual values.
Flexotron® 800
2004-08-15 11:28
System: Running
Sp:22.0°C Act:21.8°C
Type 2
The first line shows the date and time.
The second line shows the present running status.
The third line shows the present temperature setpoint and actual values.
The fourth line shows the present temperature control output values.
2004-08-15 11:28
System: Running
Sp:22.0°C Act:21.8°C
Y1:0% Y2:93% Y3:0%