37
1011-530
Separate Alarm Contacts (new default)
Contacts
Terminals
Power Is
Off
At Power-Up
No Over-Voltage
Present
At Power-Up
Over-Voltage Present
TB1-2&3
Over-voltage
Alarm
Open
State at last power-down.
If open; closed by reset.
Open; closed by reset *
TB1-4&5
Over-voltage
Alarm
Closed
State at last power-down.
If closed; opened by
reset.
Closed; opened by reset *
Terminals
Power Is
Off
At Power-Up
Software Reset Occurs
While Power Is On
TB1-7&8
Trouble Alarm
Open
Open; closed by reset
Open; closed by reset
TB2-7&8
Trouble Alarm
Closed
Closed; opened by reset
Closed; opened by reset
* after condition is cleared
Unalarmed at Power-Up With Dual (Redundant) Contacts
Contacts
Terminals
Power Is
Off
At Power-Up
No Over-Voltage
Present
At Power-Up
Over-Voltage Present
TB1-2&3
Alarm
Open
Closed
Open; closed by reset *
TB1-4&5
Alarm
Closed
Open
Closed; opened by reset *
TB1-7&8
2nd
Alarm
Open
Closed
Open; closed by reset *
TB2-7&8
2nd
Alarm
Closed
Open
Closed; opened by reset *
* after condition is cleared