19
1011-530
between the
higher
value of
U
tp
for
F
= 1 and the
lower
value of
U
tp
for
F
= 2 (=
F
c
):
Thus, the desired lockout level for this capacitor bank is 2.25%.
Formula Method
To calculate the lockout level for the capacitor bank:
A.
Calculate
V
o
for a series of steps corresponding to increasing values of
F
(up to and
including
F
c
) using the following formulas:
B.
For each value of
F
used in Step A, calculate
U
tp
:
C.
Determine the desired lockout level: the midpoint between the
U
tp
for the critical step
F
c
and the
U
tp
for
F
c-1
. (For capacitor banks with an odd number of series groups per phase,
compute alternate values of
U
tp
using the adjustment factor, then choose a lockout level
that provides the best overall response.)
Formula Method – Example 1
An installation has the following profile:
•
Highest anticipated continuous system line-to-ground voltage (
V
L-g
): 20 kV
•
Nameplate rating of the capacitor units (
V
r
): 9.96 kV
•
Number of series groups per phase (
S
): 2
•
Number of capacitor units in parallel per series group (
P
): 10
For
F
= 1,
For
F
= 2,
1.7%
2.8%
+
2
--------------------------------
2.25%
=
V
o
(volts)
P V
L
g
–
(
)
S P
F
–
(
)
F
+
-------------------------------
=
V
o
(per unit)
V
o
(volts)
V
r
------------------------
=
U
tp
(volts)
100
F
S P
F
–
(
)
F
+
-------------------------------
=
V
o
(volts)
10
20000
⋅
2 10
1
–
(
)
1
+
--------------------------------
10526 volts
=
=
V
o
(per unit)
10526
9960
---------------
1.0568 per unit (or 5.68% overvoltage)
=
=