Table 4. Alarm Output Functions.
Nominal Operating Frequency (Hz)
This is the nominal operating frequency (in Hz) for your distribution system. The
default value is “60.0.”
Password Selection
When enabled, this setpoint requires a password to make changes from the faceplate.
To enable faceplate protection, enter a 4-digit password. The range of passwords is 1 to
000to 9999. The default value is 0 - no password enabled.
Alarmed at Power-Up With Dual (Redundant) Contacts
Contacts
Terminals
Power Is
Off
At Power-Up
No Over-Voltage
Present
At Power-Up
Over-Voltage Present
TB1-2&3
Alarm
Open
Open; closed by reset
Open; closed by reset *
TB1-4&5
Alarm
Closed
Closed; opened by reset
Closed; opened by reset *
TB1-7&8
2nd
Alarm
Open
Open; closed by reset
Open; closed by reset *
TB2-7&8
2nd
Alarm
Closed
Closed; opened by reset
Closed; opened by reset *
* after condition is cleared