1011-530
42
4.
Press the ENTER button to accept the new “InstallType” setpoint value.
5.
Using the NEXT button, scroll the LCD to the “Unbal. Comp.” display.
6.
Press the ENTER button and Line 2 of the LCD will blink to indicate that the setpoint will
accept a new value.
7.
Using the + faceplate button, select the “Unbal. Comp.” setpoint value required. See Table
5.
8.
Press the ENTER button to accept the new value. The unbalance compensation feature is
now enabled, but the stored correction value is still zero and must be set.
9.
Press the ESC button to return to the “N-G Voltage” display.
10. Press the NEXT button to scroll to the “UBC In Use” display.
11. Press the UNBALANCE COMPENSATION SET button and the LCD displays “Calc
UBC” in Line 1 and the calculated value in Line 2.
12. Pressing the UNBALANCE COMPENSATION button a second time sets the unbalanced
compensation feature and “UBC In Use” is displayed in Line 1 of the LCD and the new
correction factor in Line 2. The UBC feature is now enabled and set.
NOTE: If the UNBALANCE COMPENSATION SET button is pressed, the LCD displays
“UBC In Use” in Line 1 and its correction factor in Line 2. If the unbalance compensation
feature has not been previously set, the control has not calculated and stored a UBC
correction factor, and the displayed value will be zero. When the unbalance compensation
feature is enabled, the value displayed is the correction factor currently being used. When
the unbalance compensation feature is disabled, the value displayed in Line 2 is
“Disabled”.