49
1011-530
Do one of the following:
•
Set the alarm level to a value lower than the lowest voltage just measured. Note
that this means that an alarm may occur with fewer capacitor units removed from
service.
•
Set up the unbalance compensation feature, as described in
Unbalance Compensa-
tion
on page 12.
Normal Operation
Enable Normal Control Device Operation
1. If desired, review the present status of the control device on the Operation
screen.
To display the
Operation
screen, click the Operation button at any other IntelliLINK
screen. (For a detailed explanation of the
Operation
screen, see
View the Operations
Information
in the
Troubleshooting
Instruction Sheet 1011-550.)
2. If desired, generate a report.
Generate a report if you want a printed record of the control device settings or if you
have a problem that requires help from S&C. (For details, see
Generating Reports
in
the
Operations
Instruction Sheet 1011-540.)
3. Exit the IntelliLINK software.
Select Exit from the File menu at any IntelliLINK screen, then click OK.
4. Turn off your computer, then disconnect it from the control device.
This completes the control device setup operation.