93
ENGLISH
Single installation
X
f
Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant .
X
f
If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and
liquid side service valve . Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor
PCB .
Gas side
Scale
R-410A (Inject
liquid refrigerant)
Liquid side
Vacuum port
Manifold gage
Service valve
Outdoor unit
DVM S HE_IM_DB68-05461A-08_EN.indd 93
2017-03-24 오후 1:38:43
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...