22
Preparing for installation
Model name for combination
AM580JXVHGR1 AM600JXVHGR1 AM620JXVHGR1 AM660JXVHGR1 AM660JXVHGR1 AM680JXVHGR1
Number of individual outdoor units
3
3
3
3
3
4
Combined outdoor
unit
AM080JXVHGR
AM100JXVHGR
AM120JXVHGR
2
AM140JXVHGR
1
AM160JXVHGR
1
AM180JXVHGR
AM200JXVHGR
2
1
AM220JXVHGR
2
2
1
2
3
2
Rated capacity
Cooling (kW)
163 .2
168 .2
173 .6
179 .2
184 .8
190 .4
Heating (kW)
183 .6
189 .0
195 .3
201 .6
207 .9
214 .2
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
81 .6
84 .1
86 .8
89 .6
92 .4
95 .2
Maximum (kW)
212 .3
218 .7
225 .7
233
240 .2
247 .5
Maximum number of connectable
indoor units
64
64
64
64
64
64
Model name for combination
AM700JXVHGR1 AM720JXVHGR1 AM740JXVHGR1 AM760JXVHGR1 AM780JXVHGR1 AM800JXVHGR1
Number of individual outdoor units
4
4
4
4
4
4
Combined outdoor
unit
AM080JXVHGR
AM100JXVHGR
AM120JXVHGR
1
1
1
1
1
AM140JXVHGR
1
1
AM160JXVHGR
1
AM180JXVHGR
1
AM200JXVHGR
1
AM220JXVHGR
2
2
2
2
3
3
Rated capacity
Cooling (kW)
196 .8
201 .8
207 .2
212 .8
218 .4
224 .8
Heating (kW)
221 .4
226 .8
233 .1
239 .4
245 .7
252 .9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
98 .4
100 .9
103 .6
106 .4
109 .2
112 .4
Maximum (kW)
255 .8
262 .3
269 .4
276 .6
283 .9
292 .2
Maximum number of connectable
indoor units
64
64
64
64
64
64
DVM S HE_IM_DB68-05461A-08_EN.indd 22
2017-03-24 오후 1:38:16
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...