Space requirement for installation
X
f
Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35 °C .
Larger space is required if the outdoor temperature is higher than 35 °C or if the place is heated easily by quantity
of solar radiation .
X
f
When you secure installation space, consider path for people and the direction of the wind .
X
f
Secure installation space as shown in the below illustration, considering ventilation and the service space .
X
f
If the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product .
X
f
If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if there’s
any walls around the product that may disturb the air flow . If enough ventilation space is not secured, product may
malfunction .
X
f
You may install the outdoor units with 20mm of space between the product, but product’s performance may
decrease depending on the installation environment .
Single installation
(Unit : mm)
Height of the wall is
unlimited
O
ver 100 (S2)
O
ver 500 (S1)
Over 100
Over 100
Front
side
Over 100
Over 300
<Case 1>
<Case 2>
Front side
DVM S HE_IM_DB68-05461A-08_EN.indd 26
2017-03-24 오후 1:38:17
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...