Refrigerant pipe installation
3 . Pipe installation between the outdoor units
X
f
You will need branch joints, which is an optional accessory, for connecting in between outdoor units in order to
combine outdoor units in module .
❇
❇
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units.
(Do not use T-joint)
X
f
When you install the outdoor units in module, there is no restriction of installation order among outdoor units .
X
f
Height of the connection pipe should be same or lower than the ones connected to the outdoor units .
X
f
Check the changes in comparison with the DVM
II
,
III
and
IV
.
Caution
Correct installation
Incorrect installation
Refrigerant pipes should
be connected at the
same or lower level than
the ones connected to
the outdoor unit .
Refrigerant pipes must
be connected by the side
of the product .
Straight section
should be 300mm
or more
Branch joint between
outdoor units must be
installed horizontally .
When the piping length
between outdoor unit
and the branch joint
exceeds 2m, install a
vertical trap as show in
the figure .
1 m or less
200 ~
300 mm
Over 2 m
Over 2 m
DVM S HE_IM_DB68-05461A-08_EN.indd 56
2017-03-24 오후 1:38:26
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...