14
Preparing for installation
High EER type (Heat pump)
Model name for combination
AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU AM140JXVHGH/EU AM160JXVHGH/EU
Number of individual outdoor units
1
1
1
1
1
Combined outdoor
unit
AM080JXVHGH
1
AM100JXVHGH
1
AM120JXVHGH
1
AM140JXVHGH
1
AM160JXVHGH
1
AM180JXVHGH
AM200JXVHGH
AM220JXVHGH
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
22 .4
28 .0
33 .6
40 .0
45 .0
Heating (kW)
25 .2
31 .5
37 .8
45 .0
50 .4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
11 .2
14 .0
16 .8
20 .0
22 .5
Maximum (kW)
29 .1
36 .4
43 .7
52 .0
58 .5
Maximum number of connectable
indoor units
14
18
21
26
29
Model name for combination
AM180JXVHGH/EU AM200JXVHGH/EU AM220JXVHGH/EU AM240HXVAGH/EU AM240JXVHGH1
✴
Number of individual outdoor units
1
1
1
1
2
Combined outdoor
unit
AM080JXVHGH
AM100JXVHGH
AM120JXVHGH
2
AM140JXVHGH
AM160JXVHGH
AM180JXVHGH
1
AM200JXVHGH
1
AM220JXVHGH
1
AM240HXVAGH
1
AM260HXVAGH
Rated capacity
Cooling (kW)
50 .4
56 .0
61 .6
67 .2
Heating (kW)
56 .7
63 .0
69 .3
75 .6
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
25 .2
28 .0
30 .8
33 .6
Maximum (kW)
65 .5
72 .8
80 .1
87 .4
Maximum number of connectable
indoor units
32
36
40
43
✴
: Outdoor Unit Combination has been added .
DVM S HE_IM_DB68-05461A-08_EN.indd 14
2017-03-24 오후 1:38:15
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...