64
Refrigerant pipe installation
3 . Install the distribution header horizontally .
X
f
Install the distribution header horizontally so that its ports does not face down .
Below ±10°
Horizon line
Socket
Distribution header
Pipe
(Separately purchased item)
Below ±15°
Horizon line
Horizon line
< Liquid side >
Below ±15°
Horizon line
Below ±10°
Horizon line
< Gas side >
Installing the branch joint between outdoor units
Installation of outdoor joints
Do not install the outdoor
joint in this direction .
Liquid pipe
High pressure
gas pipe
Gas pipe
❇
❇
High pressure gas pipe only applies to the H/R product .
DVM S HE_IM_DB68-05461A-08_EN.indd 64
2017-03-24 오후 1:38:31
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...