27
ENGLISH
Module installation
<Case 3>
O
ver 500
O
ver 500
O
ver 600
Over 100 Over 100
Over 100
Over 100
Over 100
Over 100 Over 100
Over 100
Front side
Front side
<Case 1>
<Case 2>
O
ver 200
O
ver 100
O
ver 300 (S2)
O
ver 500 (S1)
Over 100
Over 100
Over 100
Over 300
Over 400
Over 400
Height of
the wall is
unlimited
Front
side
Front side
❇
❇
For <Case 1> or <Case 3>
• Height of the wall on the front side should not be higher than 1500mm .
• Height of the wall on the air inlet side should not be higher than 500mm .
• Height of the wall on the side is not limited .
• If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded distance] should be added to the service space (S1, S2) .
1500
h1
500
h2
Fron
t side
Air inlet side
(Unit : mm)
S1+h1/2
S2+h2/2
DVM S HE_IM_DB68-05461A-08_EN.indd 27
2017-03-24 오후 1:38:17
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...