• This device is intended for the connection to a power supply system with a maximum permissible system
impedance shown in the table (on the left page) at the interface point (power service box) of the user’s
supply .
• The user must ensure that this device is connected only to a power supply system which fulfills the
requirement above . If necessary, the user can ask the public power supply company for the system
impedance at the interface point .
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than
or equal to Ssc(*2) at the interface point between the user’s supply and the public system . It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit power
Ssc greater than or equal to Ssc(*2) .
[Ssc (*2)]
Model
Ssc [MVA]
Model
Ssc [MVA]
AM080JXVHG
✴
3 .1
AM180JXVHG
✴
7 .6
AM100JXVHG
✴
4 .5
AM200JXVHG
✴
8 .1
AM120JXVHG
✴
5 .3
AM220JXVHG
✴
8 .6
AM140JXVHG
✴
5 .3
AM240HXVAG
✴
13 .1
AM160JXVHG
✴
6 .6
AM260HXVAG
✴
8 .9
Model
Ssc [MVA]
Model
Ssc [MVA]
AM080JXVAG
✴
3 .1
AM160JXVAG
✴
6 .6
AM100JXVAG
✴
4 .5
AM180JXVAG
✴
7 .6
AM120JXVAG
✴
5 .3
AM200JXVAG
✴
8 .1
AM140JXVAG
✴
5 .3
AM220JXVAG
✴
8 .6
NOTE
Caution for electrical work
• You must install ELCB or MCCB + ELB
- ELCB: Earth leakage breaker
- MCCB: Molded case circuit breaker
- ELB: Earth leakage breaker
• Do not operate the outdoor unit before completing the refrigerant pipe work .
• Do not disconnect or change the cable inside the product . It may cause damage to the product .
• Specification of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30 °C/ single multi conductor cables . If the condition is different from the ones
stated, please consult an electrical installation expert and re-select the power cable .
- If the length of power cable exceed 50m, re-select the power cable considering the voltage drop .
• Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover) .
• Do not use the power cable with the core wire exposed due to insulator damage occurred during removal
of the sheath . When the core wire is exposed, it may cause fire .
Insulator (inner cover)
Exposed wire
core
<The example of exposed core wire>
Sheath (outer cover)
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 73
2017-03-24 오후 1:38:33
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...