52
Refrigerant pipe installation
Connecting the flared pipes
X
f
Check if the flaring is properly done according to the standard size .
X
f
Align the center of the piping and tighten the flare nut with your hands . Then, tighten the flare nut with torque
wrench in a direction of the arrow indicated in below illustration .
X
f
Make sure to use ester oil to coat the flare connection section .
Flare connection
section
Flare nut
Pipe
Monkey
wrench
Torque wrench
Outer diameter (D, mm) Connection torque (N·m) Flare dimension (L, mm)
Flare shape (mm)
Ø 6 .35
14~18
8 .7~9 .1
90° ±2°
45° ±2°
L
D
R 0 .4~0 .8
Ø 9 .52
34~42
12 .8~13 .2
Ø 12 .70
49~61
16 .2~16 .6
Ø 15 .88
68~82
19 .3~19 .7
Ø 19 .05
100~120
23 .6~24 .0
• Blowing Nitrogen gas should be done when welding the pipe .
• Make sure to use the provided flare nut .
• Make sure that there are no cracks or twisted part when you need to bend the pipe .
• Do not fasten the flare nut with excessive strength .
• R-410A is a high pressure refrigerant and there is a risk of refrigerant leakage if the flare connection is not
coated with ester oil . Therefore, apply ester oil to coat the flare connection area .
CAUTION
DVM S HE_IM_DB68-05461A-08_EN.indd 52
2017-03-24 오후 1:38:23
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...