20
Preparing for installation
High EER type (Heat recovery)
Model name for combination
AM080JXVHGR/EU AM100JXVHGR/EU AM120JXVHGR/EU AM140JXVHGR/EU AM160JXVHGR/EU
Number of individual outdoor units
1
1
1
1
1
Combined outdoor
unit
AM080JXVHGR
1
AM100JXVHGR
1
AM120JXVHGR
1
AM140JXVHGR
1
AM160JXVHGR
1
AM180JXVHGR
AM200JXVHGR
AM220JXVHGR
Rated capacity
Cooling (kW)
22 .4
28 .0
33 .6
40 .0
45 .0
Heating (kW)
25 .2
31 .5
37 .8
45 .0
50 .4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
11 .2
14 .0
16 .8
20 .0
22 .5
Maximum (kW)
29 .1
36 .4
43 .7
52 .0
58 .5
Maximum number of connectable
indoor units
14
18
21
26
29
Model name for combination
AM180JXVHGR/EU AM200JXVHGR/EU AM220JXVHGR/EU AM240JXVHGR1
AM260JXVHGR1
Number of individual outdoor units
1
1
1
2
2
Combined outdoor
unit
AM080JXVHGR
AM100JXVHGR
AM120JXVHGR
2
1
AM140JXVHGR
1
AM160JXVHGR
AM180JXVHGR
1
AM200JXVHGR
1
AM220JXVHGR
1
Rated capacity
Cooling (kW)
50 .4
56
61 .6
67 .2
73 .6
Heating (kW)
56 .7
63
69 .3
75 .6
82 .8
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
25 .2
28
30 .8
33 .6
36 .8
Maximum (kW)
65 .5
72 .8
80 .1
87 .4
95 .7
Maximum number of connectable
indoor units
32
36
40
43
47
DVM S HE_IM_DB68-05461A-08_EN.indd 20
2017-03-24 오후 1:38:16
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...