Refrigerant pipe installation
H/R
(A)
(B)
33 .6 kW 40 .0 kW
(D)
(E)
(F)
(C)
(3)
(2)
(1)
61 .6 kW
Ex.) 135.2 kW
Capacity (kW)
No.
Pipe size (mm)
Liquid pipe
Gas pipe
High pressure
gas pipe
33 .6 kW
(1)
Ø 12 .70
Ø 28 .58
Ø 19 .05
73 .6 kW
(2)
Ø 19 .05
Ø 34 .92
Ø 28 .58
135 .2 kW
(3)
Ø 19 .05
Ø 41 .28
Ø 34 .92
Size of the pipe connected to the outdoor unit (A)
Select the size of the pipe according to the below table .
Outdoor unit capacity
(kW)
Main pipe length within 90m
Size Up (Main pipe length over 90m)
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
22 .4 kW
Ø 9 .52
Ø 19 .05
Ø 15 .88
Ø 12 .70
Ø 19 .05
Ø 15 .88
28 .0 kW
Ø 22 .22
Ø 19 .05
Ø 22 .22
Ø 19 .05
33 .6 kW
Ø 12 .70
Ø 28 .58
Ø 15 .88
Ø 28 .58
40 .0 kW
Ø 22 .22
Ø 22 .22
45 .0 kW
50 .4 kW
Ø 15 .88
Ø 19 .05
56 .0 kW
Ø 28 .58
Ø 28 .58
61 .6 kW
67 .2 kW
Ø 34 .92
Ø 34 .92
72 .8 kW ~ 84 .0 kW
Ø 19 .05
Ø 22 .22
89 .6 kW ~ 95 .2 kW
101 .6 kW
Ø 41 .28
Ø 34 .92
Ø 41 .28
Ø 34 .92
106 .6 kW ~ 135 .2 kW
140 .2 kW ~ 168 .2 kW
173 .6 kW ~ 224 .8 kW
Ø 22 .22
Ø 53 .98
Ø 41 .28
Ø 25 .40
Ø 53 .98
Ø 41 .28
Note1) If Ø 25 .40 pipe is not available on site, use Ø 28 .58 pipe .
❇
❇
For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
DVM S HE_IM_DB68-05461A-08_EN.indd 42
2017-03-24 오후 1:38:20
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...