38
Refrigerant pipe installation
H/P
33 .6 kW
40 .0 kW
(D)
(E)
(C)
(A)
(B)
(3)
(2)
(1)
61 .6 kW
Ex.) 135.2 kW
Capacity (kW)
No.
Pipe size (mm)
Liquid pipe
Gas pipe
33 .6 kW
(1)
Ø 12 .70
Ø 28 .58
73 .6 kW
(2)
Ø 19 .05
Ø 34 .92
135 .2 kW
(3)
Ø 19 .05
Ø 41 .28
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table .
Outdoor unit capacity (kW)
*Maximum pipe length within 90m
(Main pipe diameter)
*Maximum pipe length over 90m
(Main pipe diameter)
Liquid pipe (mm)
gas pipe (mm)
Liquid pipe (mm)
gas pipe (mm)
22 .4 kW
Ø 9 .52
Ø 19 .05
Ø 12 .70
Ø 22 .22
28 .0 kW
Ø 22 .22
Ø 25 .40
note1)
33 .6 kW
Ø 12 .70
Ø 28 .58
Ø 15 .88
Ø 28 .58
40 .0 kW
45 .0 kW
Ø 31 .75
note2)
50 .4 kW
Ø 15 .88
Ø 19 .05
56 .0 kW
61 .6 kW
67 .2 kW
Ø 34 .92
Ø 38 .10
note3)
72 .8 kW ~ 84 .0 kW
Ø 19 .05
Ø 22 .22
89 .6 kW ~ 95 .2 kW
101 .6 kW
Ø 41 .28
Ø 41 .28
106 .6 kW ~ 135 .2 kW
140 .2 kW ~ 168 .2 kW
Ø 53 .98
173 .6 kW ~ 224 .8 kW
Ø 22 .22
Ø 53 .98
Ø 25 .40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit .
Note1) If Ø 25 .40 pipe is not available on site, use Ø 28 .58 pipe .
Note2) If Ø 31 .75 pipe is not available on site, use Ø 34 .92 pipe .
Note3) If Ø 38 .10 pipe is not available on site, use Ø 41 .28 pipe
DVM S HE_IM_DB68-05461A-08_EN.indd 38
2017-03-24 오후 1:38:20
Summary of Contents for AM080JXVHGH/EU
Page 118: ...118 DVM S HE_IM_DB68 05461A 08_EN indd 118 2017 03 24 오후 1 38 49 ...
Page 119: ...119 ENGLISH DVM S HE_IM_DB68 05461A 08_EN indd 119 2017 03 24 오후 1 38 49 ...
Page 120: ...120 MEMO DVM S HE_IM_DB68 05461A 08_EN indd 120 2017 03 24 오후 1 38 49 ...
Page 121: ...121 ENGLISH MEMO DVM S HE_IM_DB68 05461A 08_EN indd 121 2017 03 24 오후 1 38 49 ...