1. SAFETY REGULATIONS AND INFORMATION

Read these operating instructions carefully before starting work on the
device. Observe the following warnings to prevent malfunctions or
danger to persons.
These operating instructions are to be regarded as part of the device.
The device is only to be sold or passed on together with the operating
instructions.
These operating instructions may be duplicated and distributed to inform
about potential dangers and their prevention.

1.1 Hazard levels for warnings

1

1.1 Hazard levels for warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which will result in
death or serious injury if the specified actions are not taken.
Compliance with the instructions is imperative.

WARNING

Indicates a potentially hazardous situation which can result in
death or serious injury if the specified actions are not taken.
Exercise extreme caution while working.

CAUTION

Indicates a potentially hazardous situation which can result in
minor or moderate injury or damage to property if the specified
actions are not taken.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualifications

1

1.2 Staff qualifications

The device may only be transported, unpacked, installed, operated,
maintained and otherwise used by suitably qualified, trained and
authorized technical staff.
Only authorized specialists are permitted to install the device, to carry
out a test run and to perform work on the electrical installation.

1.3 Basic safety rules

1

1.3 Basic safety rules

The safety hazards associated with the device must be assessed again
following installation in the final product.
The locally applicable industrial safety regulations are always to be
observed when working on the device.
Keep the workplace clean and tidy. Untidiness in the work area
increases the risk of accidents.
Note the following when working on the device:

;

Do not perform any modifications, additions or conversions on the
device without the approval of ebm-papst.

1.4 Voltage

1

1.4 Voltage

;

Check the device's electrical equipment at regular intervals; see
Chapter 6.2 Safety inspection.

;

Replace loose connections and defective cables immediately.

DANGER
Electrically charged device

Risk of electric shock
→ When working on an electrically charged device, stand on a

rubber mat.

2

1.5 Safety and protective features

2

1.6 Electromagnetic radiation

2

1.7 Mechanical movement

2

1.8 Emissions

2

1.9 Hot surface

2

1.10 Transport

2

1.11 Storage

3

2. INTENDED USE

4

3. TECHNICAL DATA

4

3.1 Product drawing

5

3.2 Nominal data

5

3.3 Data according to Commission Regulation (EU) 327/2011

5

3.4 Technical description

6

3.5 Mounting data

6

3.6 Transport and storage conditions

6

3.7 Electromagnetic compatibility

6

4. CONNECTION AND STARTUP

6

4.1 Mechanical connection

6

4.2 Electrical connection

8

4.3 Factory settings

9

4.4 Connection diagram

10

4.5 Checking connections

10

4.6 Switching on the device

10

4.7 Switching off the device

10

5. INTEGRATED PROTECTIVE FEATURES

10

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

11

6.1 Cleaning

12

6.2 Safety inspection

12

6.3 Disposal

Item no. 50187-5-9970 · ENU · Change 205336 · Approved 2020-10-01 · Page 1 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A3G800-AO84-01

Page 1: ...nly authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety haz...

Page 2: ...contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be eject...

Page 3: ...tructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formati...

Page 4: ...m 1 Direction of air flow V 2 Clearance for screw 12 16 mm 3 Cable PVC AWG18 6x crimped ferrules 4 Cable PVC AWG22 3x crimped ferrules Item no 50187 5 9970 ENU Change 205336 Approved 2020 10 01 Page 4...

Page 5: ...cy level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 12 2 kg Size 800 mm Motor size 112 Rotor surface Painted bla...

Page 6: ...that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when removing fan from packaging...

Page 7: ...necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided...

Page 8: ...ntrol Group address 1 Fan device address 1 Max PWM 100 Min PWM 0 Save set value to EEPROM Yes Set value requirement Analog Direction of action Positive heating Item no 50187 5 9970 ENU Change 205336 A...

Page 9: ...r failure 2 A max 250 VAC min 10 mA AC1 1 7 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 k SELV 2 10 P orange Do not use 2 11 1...

Page 10: ...ower supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the...

Page 11: ...aning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of i...

Page 12: ...the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be...