ENGLISH-23
02
INST
ALL
ATION
H
o
w t
o
c
o
nnect y
o
ur extended p
o
wer cables
1. Prepare the following tools.
T
oo
ls
Crimping pliers
Connection sleeve (mm)
Insulation tape
Contraction tube (mm)
Spec
MH-14
20xØ6.5(HxOD)
Width 19mm
70xØ8.0(LxOD)
Shape
2. As shown in the
fi
gure, peel o
ff
the shields from the rubber and wire of the
power cable.
- Peel o
ff
20 mm of cable shields from the pre-installed tube.
•
For information about the power cable speci
fi
cations for indoor and
outdoor units, refer to the installation manual.
•
After peeling o
ff
cable wires from the pre-installed tube, insert a
contraction tube.
CAUTION
20
Pre-installed tube for the power cable
(Unit: mm)
120
60
20
20
20
180
Power cable
3. Insert both sides of core wire of the power cable into the connection sleeve.
f
Meth
o
d 1
Push the core wire into the sleeve from both sides.
Connection sleeve
f
Meth
o
d 2
Twist the wire cores together and push it into the sleeve.
Connection sleeve
4. Using crimping tool, compress the two points and
fl
ip it over and compress another two points in the same location.
- The compression dimension should be 8.0.
- After compressing it, pull both sides of the wire to make sure it is
fi
rmly pressed.
Compression
dimension
f
Method 1
Compress it 4 times.
5 mm
f
Method 2
Compress it 4 times.