82 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
during fault
0x00~0x11
LED ones:
0:
Action under fault undervoltage
1:
No action under fault undervoltage
LED tens:
0:
Action during the automatic reset
1:
No action during the automatic reset
P11.14
Speed
deviation
detection
0.0~50.0%
Set the speed deviation detection time.
10.0%
○
P11.15
Speed
deviation
detection time
This parameter is used to set the speed deviation detection
time.
Setting range of P11.15: 0.0~10.0s
0.5s
○
P11.16
Automatic
frequency
decreasing at
voltage drop
0:
Invalid
1:
Valid; ensure rated output torque when voltage drop
0x00
○
P13 Group Control parameters of Short circuit braking
P13.13
Braking
current of
short circuit
After the inverter starts, when P01.00=0, set P13.14 to
non-zero value and begin short circuit braking.
After the inverter stops, when the operation frequency is less
than P01.09, set P13.15 to non-zero value and begin
stopping short-circuit braking and then DC braking.
Setting range of P13.13: 0.0~150.0% (inverters)
Setting range of P13.14: 0.00~50.00s
0.0%
○
P13.14
Braking
retention time
of starting
short circuit
0.00s
○
P13.15
Braking
retention time
of stopping
short circuit
0.00s
○