
34 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3: Static autotuning 2 (autotune part parameters)
; when
the current motor is motor 1, autotune P02.06, P02.07,
P02.08
P00.16
AVR function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the inverter can cancel the
impact on the output voltage of the inverter because of the
bus voltage fluctuation.
1
○
P00.18
Function
restore
parameter
0: No operation
1: Restore the default value
2: Clear fault records
3: Lock all function codes
Note:
The function code will restore to 0 after finishing the
operation of the selected function code.
Restoring to the default value will cancel the user password,
please use this function with caution.
0
◎
P01 Group Start-up and stop control
P01.00
Start mode
0: Start-up directly
. Start from the starting frequency
P01.01
1
: Start-up after DC braking. S
tart the motor from the
starting frequency after DC braking (set the parameter
P01.03 and P01.04). It is suitable in the cases where reverse
rotation may occur due to the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2.
The direction and speed will
be tracked automatically for the smoothing starting of
rotating motors. It suits the application with reverse rotation
when big load starting.
Note:
This function is only available
for the inverters 3PH 400V
≥
4kW and 3PH 220V
≥
1.5kW
0
◎
P01.01
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the original
frequency during the inverter starting. See P01.02 for
detailed information.
Setting range: 0.00~50.00Hz
0.50Hz
◎
P01.02
Retention time
of the starting
frequency
Set a proper starting frequency to increase the torque of the
inverter during starting. During the retention time of the
starting frequency, the output frequency of the inverter is the
starting frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set frequency is
lower than the starting frequency, the inverter will stop
0.0s
◎
Summary of Contents for CV30
Page 1: ...USER MANUAL INVERTER CONTROLVIT CV30...
Page 2: ......
Page 27: ...Keypad Operation Procedure 27 140 Figure 4 5 Sketch map of state watching...
Page 89: ...Function Parameters 89 140 5 2 Diagram of quick start...
Page 139: ......