Function Parameters
51 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
2: 3-wire control 1; SIn is the enabling terminal on this mode,
and the running command is caused by FWD and the
direction is controlled by REV. SIn is normal closed.
The direction control is as below during operation:
Sln
REV
Previous
direction
Current
direction
ON
OFF
→
ON
Forward
Reverse
Reverse
Forward
ON
ON
→
OFF
Reverse
Forward
Forward
Reverse
ON
→
OFF
ON
Decelerate to stop
OFF
3: 3-wire control 2; SIn is the enabling terminal on this mode,
and the running command is caused by SB1 or SB3 and
both of them control the running direction. SB2 (normal
closed) generates the stop command.