Function Parameters
67 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
multi-function output terminals will output the signal of
“setting counting number arrival”, the counter will clear all
numbers and stop to recount before the next pulse.
The given counting value P08.26 should be no more than the
setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25: P08.26~65535
Setting range of P08.26: 0~P08.25
P08.27
Set running
time
Pre-set running time of the inverter. When the accumulative
running time achieves the set time, the multi-function digital
output terminals will output the signal of “running time
arrival”.
Setting range: 0~65535min
0m
○
P08.28
Fault
Auto-reset
Attempts
Number of fault auto-reset attempts
: set the fault reset
attempts by selecting this function. If the reset attempts
exceed this set value, the inverter will stop for the fault and
wait to be repaired.
The interval time of the fault reset
: The interval between
the time when the fault occurs and the time when the reset
action occurs.
Setting range of P08.28: 0~10
Setting range of P08.29: 0.1~100.0s
0
○
P08.29
Interval time of
automatic fault
reset
1.0s
○
P08.30
Frequency
decreasing
ratio in drop
control
The output frequency of the inverter changes as the load.
And it is mainly used to balance the power when several
inverters drive one load.
Setting range:
-50.00Hz~50.00Hz
0.00Hz
○
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the corresponding
frequency of “
FDT electrical level detection value
”, the
multi-function digital output terminals will output the signal of
“frequency level detect FDT”. Until the output frequency
decreases to a value lower than the corresponding
frequency (
FDT retention detection value
), the signal is
valid. Below is a diagram:
50.00Hz
○
P08.33
FDT1 retention
detection value
5.0%
○
P08.34
FDT2 electrical
level detection
value
50.00Hz
○