Function Parameters
81 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
the motor or
the inverter
pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the inverter or
the motor.
Setting range: 0x000~0x131
LED ones:
0:
Overload pre-alarm of the motor, comply with the rated
current of the motor
1:
Overload pre-alarm of the inverter, comply with the rated
current of the inverter
LED tens:
0:
The inverter continues to work after underload pre-alarm
1:
The inverter continues to work after underload pre-alarm
and the inverter stops to run after overload fault
2:
The inverter continues to work after overload pre-alarm
and the inverter stops to run after underload fault
3:
The inverter stops when overloading or underloading.
LED hundreds:
0:
Detection all the time
1:
Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
P11.09
Overload
pre-alarm test
level
150%
○
P11.10
Overload
pre-alarm
detection time
1.0s
○
P11.11
Detection level
of the underload
pre-alarm
If the inverter current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the inverter
will output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
50%
○
P11.12
Detection time of
the underload
pre-alarm
1.0s
○
P11.13
Output terminal
action selection
Select the action of fault output terminals on undervoltage
and fault reset.
0x00
○