40 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P02.01
Motor rated
power
0.1~3000.0kW
Depends
on model
◎
P02.02
Motor rated
frequency
0.01Hz~P00.03 (the Max. frequency)
50.00Hz
◎
P02.03
Motor rated
speed
1~36000rpm
Depends
on model
◎
P02.04
Motor rated
voltage
0~1200V
Depends
on model
◎
P02.05
Motor rated
current
0.8~6000.0A
Depends
on model
◎
P02.06
Motor stator
resistor
0.001~65.535
Ω
Depends
on model
○
P02.07
Motor rotor
resistor
0.001~65.535
Ω
Depends
on model
○
P02.08
Motor leakage
inductance
0.1~6553.5mH
Depends
on model
○
P02.09
Motor mutual
inductance
0.1~6553.5mH
Depends
on model
○
P02.10
Motor non-load
current
0.1~6553.5A
Depends
on model
○
P02.11
Magnetic
saturation
coefficient 1 for the
iron core of motor
0.0~100.0%
80.0%
◎
P02.12
Magnetic
saturation
coefficient 2 for the
iron core of motor
0.0~100.0%
68.0%
◎
P02.13
Magnetic
saturation
coefficient 3 for the
iron core of motor
0.0~100.0%
57.0%
◎
P02.14
Magnetic
saturation
coefficient 4 for the
iron core of motor
0.0~100.0%
40.0%
◎
Summary of Contents for CV30
Page 1: ...USER MANUAL INVERTER CONTROLVIT CV30...
Page 2: ......
Page 27: ...Keypad Operation Procedure 27 140 Figure 4 5 Sketch map of state watching...
Page 89: ...Function Parameters 89 140 5 2 Diagram of quick start...
Page 139: ......