Function Parameters
59 - 140
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
sequence of
running
command
0:
Keypad control
→
terminals control
→
communication
control
1:
Keypad control
←→
terminals control
2:
Keypad control
←→
communication control
3:
Terminals control
←→
communication control
P07.04
STOP/RST
stop function
Select the stop function by STOP/RST. STOP/RST is
effective in any state for the keypad reset.
0:
Only valid for the keypad control
1:
Both valid for keypad and terminals control
2:
Both valid for keypad and communication control
3:
Valid for all control modes
0
○
P07.05
Displayed
parameters 1
of running state
0x0000~0xFFFF
BIT0:
running frequency (Hz on)
BIT1:
set frequency(Hz flickering)
BIT2:
bus voltage (Hz on)
BIT3:
output voltage (V on)
BIT4:
output current (A on)
BIT5:
running rotation speed (rpm on)
BIT6:
output power (% on)
BIT7:
output torque (% on)
BIT8:
PID reference (% flickering)
BIT9:
PID feedback value (% on)
BIT10:
input terminals state
BIT11:
output terminals state
BIT12:
torque set value (% on)
BIT13:
pulse counter value
BIT14:
reserved
BIT15:
PLC and the current stage of multi-step speed
Example-
Default value: 0000 0011 1111 1111
0x03FF
○
P07.06
Displayed
parameters 2
of running state
0x0000~0xFFFF
BIT0:
analog AI1 value (V on)
BIT1:
analog AI2 value (V on)
BIT2:
analog AI3 value (V on)
BIT3:
high speed pulse HDI frequency
BIT4:
motor overload percentage (% on)
BIT5:
the inverter overload percentage (% on)
0x0000