48 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P04.32
Output
minimum
voltage
The setting range of P04.32: 0.0%~ P04.31
0.0%
◎
P04.33
Weakening
coefficient in
constant
power zone
Adjust the output voltage of the inverter in SVPWM mode
when weakening.
Note:
Invalid in the constant torque mode.
The setting range of P04.33: 1.00~1.30
1.00
○
P05 Group Input terminals
P05.00
HDI input
selection
0: HDI is high pulse input
. See P05.49~P05.54
1: HDI is switch input
(same as S1
~
S4 terminals)
0
◎
P05.01
S1 terminals
function
selection
Note
: S1~S4 and HDI are terminals on the control board,
and P05.12 can be used to set the function of S5~S8, that
are virtual terminals
0:
No function
1:
Forward rotation operation
2:
Reverse rotation operation
3:
3-wire control operation
4:
Forward jogging
5:
Reverse jogging
6:
Coast to stop
7:
Fault reset
8:
Operation pause
9:
External fault input
1
◎
P05.02
S2 terminals
function
selection
4
◎
P05.03
S3 terminals
function
selection
7
◎
P05.04
S4 terminals
function
selection
0
◎