122 - 140
Communication protocol
If the response message is as below:
ASCII mode:
The command sent to the inverter:
If the response message is as below:
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
P00.11
ACC time 1 Setting range of P00.11 and P00.12:
0.0~3600.0s
Depends on model
○
P00.12
DEC time 1
Depends on model
○
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to 0064H, and the DEC
time of 20s corresponds to 00C8H.
RTU mode:
The command sent to the inverter:
If the response message is as below:
ASCII mode:
The command sent to the inverter: