Installation Guidelines
15 - 140
Environment
Conditions
Altitude
Below 1000m
If the sea level is above 1000m, please derate 1% for every additional 100m.
Vibration
≤
5.8m/s
2
(0.6g)
Installation direction
The inverter should be installed on an upright position to ensure sufficient
cooling effect.
Note:
CV30 inverters should be installed in a clean and ventilated environment according to enclosure
classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The inverter may be installed on the wall or in a cabinet.
The inverter needs to be installed in the vertical position. Check the installation site according to the
requirements below.
Refer to chapter
Dimension Drawings
in the appendix for frame details.
3.1.3 Installation manner
(1) Wall and rail mounting for the inverters 1PH 230V-3PH 400V
≤
2.2kW and 3PH 220V
≤
0.75kW:
a)
Wall mounting b) Rail mounting
Figure 3-1 Installation
Note: the minimum space of A and B is 100mm if H is 36.6mm and W is 35.0mm.
(2) Wall and flange mounting for the inverters 3PH 400V
≥
4kW and 3PH 220V
≥
1.5kW: