54 - 140
Fault Tracking
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
lower limit of
AI2
Input filter time
: this parameter is used to adjust the
sensitivity of the analog input. Increasing the value properly
can enhance the anti-interference of the analog, but weaken
the sensitivity of the analog input
Note:
AI1 supports 0~10V input and AI2 supports 0~10V or
0~20mA input, when AI2 selects 0~20mA input, the
corresponding voltage of 20mA is 10V. AI3 can support an
input of -10V~+10V.
The setting range of P05.32: 0.00V~P05.34
The setting range of P05.33: -100.0%~100.0%
The setting range of P05.34: P05.32~10.00V
The setting range of P05.35: -100.0%~100.0%
The setting range of P05.36: 0.000s~10.000s
The setting range of P05.37: 0.00V~P05.39
The setting range of P05.38: -100.0%~100.0%
The setting range of P05.39: P05.37~10.00V
The setting range of P05.40: -100.0%~100.0%
The setting range of P05.41: 0.000s~10.000s
The setting range of P05.42: -10.00V~P05.44
The setting range of P05.43: -100.0%~100.0%
The setting range of P05.44: P05.42~P05.46
The setting range of P05.45: -100.0%~100.0%
The setting range of P05.46: P05.44~10.00V
The setting range of P05.48: 0.000s~10.000s
P05.39
Upper limit of
AI2
10.00V
○
P05.40
Corresponding
setting of
the upper limit
of AI2
100.0%
○
P05.41
AI2 input filter
time
0.100s
○
P05.42
Lower limit of
AI3
-10.00V
○
P05.43
Corresponding
setting of the
lower limit of
AI3
-100.0%
○
P05.44
Middle value of
AI3
0.00V
○
P05.45
Corresponding
middle setting
of AI3
0.0%
○
P05.46
Upper limit of
AI3
10.00V
○
P05.47
Corresponding
setting of
the upper limit
of AI3
100.0%
○
P05.48
AI3 input filter
time
0.100s
○
P05.50
Lower limit
frequency of
HDI
Setting Range: 0.000 kHz~P05.52
0.000
kHz
○
P05.51
Corresponding
setting of HDI
low frequency
-100.0%~100.0%
0.0%
○