Installation Guidelines
3.2.3 Wiring of terminals in main circuit
1. Fasten the grounding conductor of the input power cable with the grounding terminal of the inverter (
PE
)
by
360
degree grounding technique. Connect the phase conductors to
L1
,
L2
and
L3
terminals and fasten.
2. Strip the motor cable and connect the shield to the grounding terminal of the inverter by
360
degree
grounding technique. Connect the phase conductors to
U
,
V
and
W
terminals and fasten.
3. Connect the optional brake resistor with a shielded cable to the designated position by the same
procedures in the previous step.
4. Secure the cables outside the inverter mechanically.
3.2.4 Wiring diagram of control circuit
Figure 3-9 Wiring of control circuit
3.2.5 Terminals of control circuit
Figure 3-10 Terminals of control circuit
Type
Terminal name
Function
description
Technical specifications
Communication
485+
RS485
communication
RS485 communication interface
485-
Digital
input/output
S1
Digital input
1. Internal impedance: 3.3k
Ω
2. 12~30V voltage input is available
3. The terminal is dual-direction type
S2
S3