Technical data’s and circuit diagrams for the modular system
PCD0
26/766 E2
(HB_PCD0 26 766_E2.DOC)
SAIA-Burgess Controls Ltd.
Page 87
4.18.5
Basic functions RIO C24-10
The following basic functions are active after the power supply has
been switched on:
·
Actual counter values = 0
·
Counter start values = 0
·
4 16 bit counters (2 32 bit counters can be set in control data word
5)
·
Interference suppression for counting frequencies up to 20 kHz
·
Every counter counts the input signals as long as the enable
signal (gate) is set.
·
Counting method: Up to the respective minimum/maximum value,
no reset when the maximum number is reached
Data configuration 4 counters 16 bit
Word
Input
Output
1
Actual value counter 1
Start value counter 1
2
Actual value counter 2
Start value counter 2
3
Actual value counter 3
Start value counter 3
4
Actual value counter 4
Start value counter 4
5
Control state of terminals X1.0 ... X1.7
and X2.0 ... 2.7
Control data
(see next table)
Control data word 5
Bit
Value
Function
0-7
No function
8-10
0
For optional functions
11
i0
4 counters 16 bit
12
1
Set counter 1 to start value
13
1
Set counter 2 to start value
14
1
Set counter 3 to start value
15
1
Set counter 4 to start value
Data configuration 2 counters 32 bit
Word
Input
Output
1
Counter 1 MSB
Counter 1 start MSB value
2
Counter 1 actual LSB value
Counter 1 start LSB value
3
Actual value counter 2
Start value counter 2
4
Actual value counter 2
Start value counter 2
5
Control state of terminals X1.0 ... X1.7 and X2.0 ...
2.7
Control data
(see next table)
Control data word 5
Bit
Value
Function
0-7
No function
8-10
For optional functions
11
Always 1
Selection: Module operates as 2x 32 bit counter
12
1
Set counter 1 to start value
13
No function
14
1
Set counter 2 to start value
15
No function