4.16.4
Terminal assignment RIO T10-10
No external bridges to unconnected terminals are required when using
2- and 3-wire connections.
4.16.5
Specifications RIO T10-10
RIO T10-10
Order no.
PCD0.W540
Module ID
14d / 0Eh
Number of inputs
4, automatically adjusting to Pt100 / Pt1000
Temperature sensor
Pt100 / Pt1000
Measuring range
-100°C to +450°C
Typical
<±1°C
Measuring error
Max.
±0.3°C ±0.25% from measured value
Resolution
0.1°C
A/D converter
16 bits
Integration period
< 100 ms
External power supply
DC 24 V ± 20% max. 5% residual ripple
Power consumption from external 24 V power supply
3.8 W (including load current 4 x Pt100)
Power consumption from internal 5 V power supply
0.325 W