PCD0
Technical data
Page 162
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
11
Technical data
Climatic conditions
Ambient operating temperature
0 ... +55°C (class KV to DIN 40040), vertical installation, free air circulation
Storage temperature
-25 ... +70°C (class HS to DIN 40040)
Relative humidity
30 ... 95% (class F, DIN 40040), no condensation
Air pressure in operation
860 ... 1060 hPa
Mechanical strength
Vibration
DIN IEC 68-2-6
10 ... 57Hz constant amplitude 0.075mm
57 ... 150Hz constant acceleration 1g
Electrical safety
Protection class
IP 20 to EN 60529
Clearance/creepage distance
DIN EN 61131-2 and DIN EN 50178 between electrical circuits and objects
as well as between electrically isolated circuits in accordance with
overload category II, contamination level 2
Test voltage
350VAC/50Hz for rated equipment voltage 24VDC
Electromagnetic compatibility
Electrostatic discharge
EN 61000-4-2: 4kV contact discharge
Electromagnetic fields
EN 61000-4-3: Field intensity 10V/m, 80 ... 1000MHz
Burst
EN 61000-4-4: 2KV on DC supply lines, 1KV on I/O signal and serial
interface lines
Interference emissions
EN 55011: Class A, Group 1
Mechanical and installation
Housing material
PA 6.0 GF20 black
Rail
DIN rail EN 50022-35
Connection system
Connection
Spring terminal
Conductor size
Finely stranded*: 0.14-1.5mm
2
single-core: 0.5-2.5mm
2
*If a wire end ferrule is used it must be pressed air-tight.
Stripping length
10mm BC bus coupler, all I/O modules for modular system and
compact RIO’s
9mm EC bus coupler