Operating modes of the BC bus coupler
PCD0
26/766 E2
(HB_PCD0 26 766_E2.DOC)
SAIA-Burgess Controls Ltd.
Page 135
Display of the last 20 I/O maps
Return to TRIGGER mode when the trigger condition has been
fulfilled. E-00 is displayed. The last current input map when the trigger
condition occurred is now displayed as a yellow LED on the expansion
module. Use the Left key to see the previous map. The display will
show the previous number E=n (n=0..19). Use the Right key to display
the next map.
Use the High key to set the display to input and the Low key to set it to
output.
Resetting the trigger condition
Press the Mode key to select TRIGGER. Press OK to confirm your
selection.
Trigger condition is not fulfilled:
Move the channel cursor to the channel which you want to reset and
press OK 3 times.
3X
This deletes one trigger condition. The display briefly looks as follows:
Trigger condition is fulfilled:
If a trigger condition has been fulfilled delete all the trigger conditions
and the trigger buffer by pressing OK 3 times.
Trigger conditions are not
permanently stored. They are, however,
stored until the bus coupler is switched off.