PCD0
Service functions on the BC bus coupler
Page 142
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
9.12
Service function 10
Byte swap mode
Byte swap mode changes the assignment of input/output data to the
I/O maps.
Parameter = 0
OFF
Parameter = 1
ON for all digital expansion modules
Parameter = 2
ON for all digital expansion modules, counter,
positioning and analog modules, and diagnosis
data
Parameter = 3
ON for all counter, positioning and analog
modules, and diagnosis data
Default setting: Parameter 0
9.13
Service function 11 Delete bus coupler EEPROM
All settings for the bus node configuration, bus address, lock masks
and service functions are deleted or set to the default setting.
Parameter <>15
Parameter = 15
No changes
EEPROM is deleted, the default settings are set.
Press OK to confirm the service function. The following delete
message appears:
You have to switch the bus coupler power supply off and on after the
delete message has disappeared.
9.14
Service function 12
Display/set bus address
Displays the bus address.
Change the bus address using the keypad on the bus coupler. The
keys have the following values: