Technical data’s and circuit diagrams for the modular system
PCD0
26/766 E2
(HB_PCD0 26 766_E2.DOC)
SAIA-Burgess Controls Ltd.
Page 51
4.8.2
Data width, addressing and terminal assignment RIO 4 O R
RIO 4 O R
Bytes Inputs
Bytes Outputs
Data width
Byte 1
Byte 2
Not used
Bit
Terminal
0
X3.0/4.0
1
X3.1/4.1
2
X3.2/4.2
3
X3.3/4.3
4
5
6
7
Not
used
The Bit position can be changed with the
Byte-Swap instruction. See page 159.
1 Byte start addresses
2 Bit numbering
4.8.3
Specifications RIO 4 O R
RIO 4 O R
Order no.
PCD0.A200
Module ID
19d / 13h
Number of outputs
4
External power supply
DC 24 V ± 20% max. 5% residual ripple
Power consumption from external 24 V power
supply
2 W
Power consumption from internal 5 V power
supply
0.25 W
Outputs
Output current per output max.
5 A
Total current for whole module max.
12 A
Minimum contact load
AC/DC 5 V / 10 mA
Rated operating voltage
AC/DC 24 to 240 V
Utilization category according to IEC 60947-5-1
AC-15 U
e
AC 230 V, I
e
3 A
DC-13 U
e
DC 24 V, I
e
2 A
Permissible frequency of operation
£
3600 operating cycles / h
Mechanical life
30 x 10
6
operating cycles
Electrical life
20/2 A, AC 250 V, cos
j
= 0.3
0.12 x 10
6
operating cycles AC-15
Isolation from internal bus
Yes, each channel separately relay contact
Simultaneity
100%
Free-wheeling diode
Integrated
Signal delay
<100
µ
s (hardware) see also Response Times section on
See also General specifications on page 162.