![Roth BW/H Komfort Installation Manual Download Page 60](http://html1.mh-extra.com/html/roth/bw-h-komfort/bw-h-komfort_installation-manual_1491200060.webp)
BW/H Komfort
48000120_r
oth_bwh_k
omf
or
t.mon06304.ind
d
|
60
Adjustment range: -5 ... +45 K
Factory setting: 5 K
Adjustment channel for the day correction of the heating
curcuit. The day correction is always activating outlying of
the 3 time frames of the night correction. The set flow
temperature will be dropped or risen by the adjusted tem-
perature difference.
Day corr.:
Adjustment channel for the maximum tolerable flow tem-
perature of the heating curcuit. By exeeding the maximum
flow temperature the heating curcuit will be switched off
(the pump is deactivated and the mixer is closed).
Adjustment range: 10 ... +100 °C
Factory setting: 50 °C
Tflowmax:
Dependance of the flow temperature, the outside tempe-
rature and the chosen heating curve.
Heating curve:
Adjustment range: 0,3 ... 3,0
Factory setting: 1,0
Heating curve
Outside temperature in °C
Feed flo
w temperatur
e in °C