BW/H Komfort
48000120_r
oth_bwh_k
omf
or
t.mon06304.ind
d
|
56
DVGW:
The DVGW-function controls if the temperature at the gi-
ven sensor (Sen-DVGW) exceeds a temperature of 60 °C.
If 60 °C are not reached up to DVGW start time, this func-
tion is activated in order to activate e.g. an after-heating.
The function is switched-off when 60 °C are reached at the
relevant sensor or at midnight (reset).
If the relevant sensor does not work, this function is sus-
pended.
CS-Bypass:
f the irradiation exceeds the adjusted value CS-bypass, so
that the collector circuit is operated.
It is switched-off if the irradiation falls 2 minutes below the
value CS-bypass.
The collector circuit is operated with minimum pump
speed.
CS-Bypass:
Adjustment range 100 ... 500 W/m
2
Factory setting 200 W/m
2
2-collector systems:
If a loading of the stores is effected in these systems, the
function is switched-off.
Recooling:
This function is used for keeping the system temperatures
and consequently the thermal load as low as possible.
If all stores of a system have exceeded the maximum tem-
perature, the loading circuit for 1st store is again operated
in order to reduce the surplus energy from tubes and
collector.
This „circulation“ is again switched-off if the maximum store
temperature is underrun by 2 K.
2-collector systems:
Both collector circuits are activated in a 2-collector sys-
tem.
Combined with collector cooling function:
If the option „collector cooling“ is activated in addition to
the recooling function, the response action of the recoo-
ling function changes. The objective is now to dissipate the
energy supplied by the collector cooling.
If the temperature at the collector decreases by 5 K below
that of the store, the recooling function is activated and the
loading circuit is again operated (for cooling of the store).
If the difference between collector and store decreases
below 3 K during that cooling period, the function is swit-
ched-off.
2-collector systems:
In a 2-collector system, the collectors are separately opera-
ted due to the above-desribed switch-on conditions.
Activating: Tst
≥
Tstmax
Hysteresis 2 K
Activation: (Tst-Tcol)
≥
5 K
Deactivation: (Tst-Tcol) < 3 K
B
Summary of Contents for BW/H Komfort
Page 34: ......
Page 68: ......
Page 102: ......
Page 136: ......
Page 137: ...Roth BW H Komfort Manual Roth BW H Komfort Montaje Conexiones Funcionamiento Errores Ejemplos...
Page 170: ...BW H Komfort 48000120_roth_bwh_komfort mon06304 indd 170...
Page 171: ...BW H Komfort 48000120_roth_bwh_komfort mon06304 indd 171...
Page 172: ......