Install Stratix 5700 Switches
Chapter 5
European Hazardous Location Approval
The following applies to products marked
II 3 G: Such modules:
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given
in Annex II to Directive 94/9/EC. See the EC Declaration of Conformity at
http://www.rockwellautomation.com/products/certification
• The type of protection is "Ex nA nC IIC T3 Gc” according to EN 60079-15.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, air or dust mixtures are unlikely to occur, or are likely to occur only infrequently and
for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 1999/92/EC.
• Comply to Standards: EN 60079-0:2012, EN 60079-15:2010, reference certificate number DEMKO 12 ATEX8694536X.
ATTENTION:
This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
Special Conditions for Safe Use
• This equipment shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at least IP54 (as
defined in IEC60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when applied
in Zone 2 environments. The enclosure must utilize a tool removable cover or door.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other
means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• The USB port is intended for temporary local programming purposes only and not intended for permanent connection and do
not use the USB port in hazardous locations.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the
rated voltage when applied in Zone 2 environments.
WARNING:
If you connect or disconnect Ethernet cables with power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION:
The alarm port cables are not to exceed 10.0 m (32.81 ft).
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......