Configure Switch Features
Chapter 7
Active Supervisor Precedence
Displays the precedence that is assigned to the ring supervisor.
You assign the precedence value on the Advanced Network Configuration dialog box. See
Enable Supervisor Mode
Check to make the switch a ring supervisor. The configuration takes effect immediately.
Ring Faults Detected
Displays the number of faults that are currently detected in the ring.
When a DLR network is powered-up, the supervisor can detect ring faults as a result of powering up before other devices on the
network. You can use an MSG instruction to clear the faults.
Supervisor Status
Displays whether the switch is operating as the active ring supervisor or back-up ring supervisor.
Valid values:
• Active
• Backup
Last Active Node on Port 1
Displays the IP address of the last active node on DLR port 1.
Last Active Node on Port 2
Displays the IP address of the last active node on DLR port 2.
Table 47 - Ring 1/Ring 2/Ring 3 Fields (Continued)
Field
Description
Table 48 - Advanced Network Configuration Fields
Field
Description
Network Topology
Displays whether the switch is operating in a DLR or linear network.
Valid values:
• Ring
• Linear
Active Ring Supervisor
Displays the IP address of the active ring supervisor.
Active Supervisor Precedence
Displays the precedence that is currently assigned to the active ring supervisor.
Supervisor Mode
Displays the status of Supervisor mode. You can enable Supervisor mode on the Ring 1, Ring 2, or Ring 2 view. See
Valid values:
• Enabled
• Disabled (default)
Supervisor Precedence
Type a precedence value to assign to the ring supervisor. When multiple supervisors are configured, the precedence value determines
the active ring supervisor. Only one supervisor can be active at one time. The precedence is transmitted in beacon frames.
When two supervisors have the same precedence, the device with the numerically highest MAC address becomes the active
supervisor.
Valid values: 0…255.
The default precedence is 0.
The highest precedence is 255.
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......