52
Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
Chapter 2
Get Started
Table 15 - Port Settings
Field
Description
Port Name
The number of the switch port, including port type, such as Fa for Fast Ethernet and Gi for Gigabit Ethernet, and the specific port number:
• Gi/1 is the gigabit port 1 of the switch.
• Fa1/1 is Fast Ethernet port 1 on the switch.
Description
The description of the switch port.
We recommend that you provide a port description to help identify the port during monitoring and troubleshooting. The description can be the
location of the connected device or the name of the person using the connected device.
Port Status
The state of the switch port. The default is Enabled. You can change this setting on the Edit Physical Port window by checking or clearing the
Administrative checkbox.
We recommend disabling the port if the port is not in use and is not attached to a device.
An example of when to change this setting is during troubleshooting. You can troubleshoot a suspected unauthorized connection by administratively
disabling the port.
Speed
The operating speed of the switch port. You can choose Auto (autonegotiation) if the connected device can negotiate the link speed with the switch
port. The default is Auto.
We recommend that you use the default so that the speed setting on the switch port automatically matches the setting on the connected device.
Change the switch port speed if the connected device requires a specific speed.
An example of when to change this setting is during troubleshooting. If you are troubleshooting a connectivity problem, you can change this setting to
see if the switch port and connected device have a speed mismatch.
Duplex
The Duplex mode of the switch port:
• Auto (autonegotiation) if the connected device can negotiate with the switch.
• Full (Full-duplex mode) if both devices can send data simultaneously.
• Half (Half duplex mode) if one or both devices cannot send data simultaneously.
The default is Auto.
On Gigabit Ethernet ports, you cannot set the port to Half-duplex mode if the port speed is set to Auto.
We recommend that you use the default so that the duplex setting on the switch port automatically matches the setting on the connected device.
Change the Duplex mode on the switch port if the connected device requires a specific mode.
An example of when to change this setting is during troubleshooting. If you are troubleshooting a connectivity problem, you can change this setting to
verify if the switch port and connected device have a duplex mismatch.
Auto-MDIX
Whether the automatic medium-dependent interface crossover (auto-MDIX) feature can automatically detect the required cable connection type
(straight-through or crossover) and configure the connection appropriately. The default is Enable.
This setting is not available on the SFP module ports.
Media Type
The active port type (either the RJ45 port or the SFP module port) of a dual-purpose uplink port.
By default, the switch detects whether the RJ45 port or SFP module port of a dual-purpose port is connected and uses the port accordingly. Only one
port can be active at a time. If both ports are connected, the SFP module port has priority. You cannot change the priority setting.
Choose from the following media types:
• SFP—The SFP module port is active. If you choose this option, the speed and duplex displays the current settings and auto-MDIX displays N/A.
• RJ45—The RJ45 port is active. If you choose this option, you can set the port speed, duplex, and auto-MDIX values.
• Auto (autonegotiation)—Either port can be active. If you choose this option, the speed and duplex is set to auto and auto-MDIX displays N/A.
The default is Auto.
Operational Mode
The operational state of the port. Displays the administrative mode or Down (if disabled).
Access VLAN
The VLAN that an interface belongs to and carries traffic for, when the link is configured as or is acting as a nontrunking interface.
Administrative Mode
Displays one of the following administrative modes:
• Access—The interface is in permanent nontrunking mode and negotiates to convert the neighboring link into a nontrunk link even if the
neighboring interface is a trunk interface. If you choose this option, also choose an Access VLAN. An access port belongs to and carries the traffic of
only one VLAN (unless it is configured as a voice VLAN port).
• Trunk—The interface is in permanent trunking mode and negotiates to convert the neighboring link into a trunk link even if the neighboring
interface is not a trunk interface. If you choose this option, also choose whether to allow All VLANs or specified VLAN IDs.
• Dynamic Auto—The interface converts the link to a trunk link if the neighboring interface is set to trunk or desirable mode. This mode is the
default setting. If you choose this option, specify an Access VLAN to use when the link is in access mode. Also specify whether to allow All VLANs or
specified VLAN IDs when the link is in trunk mode.
• Dynamic Desirable—If the neighboring interface is set to Trunk, Dynamic Desirable, or Auto mode, the interface converts the link to a trunk link. If
you choose this option, specify an Access VLAN to use when the link is in access mode. Also choose whether to allow All VLANs or specified VLAN IDs
when the link is in Trunk mode.
• Routed—The interface acts like a port on a router but does not have to be connected to a router. A routed port is not associated with a particular
VLAN, as is an access port. A routed port behaves like a regular router interface, except that it does not support VLAN subinterfaces. Routed ports
can be configured with a Layer 3 routing protocol. A routed port is a Layer 3 interface only and does not support Layer 2 protocols, such as DTP and
STP. Routed ports are supported only on switches running the IP base or IP services image.
The default setting is Dynamic Auto.
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......