Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
39
AFE in IP20 2500 MCC Style Enclosure – Installation/Wiring
Chapter 1
To disconnect the common mode capacitors, remove the upper guard and then
remove the jumpers that are shown in
. For more information on
ungrounded system installation, see Wiring and Grounding Guidelines for
Pulse Width Modulated (PWM) AC Drives, publication
.
Figure 21 - AFE Frame 13 LCL Filter Common Mode Capacitor Jumper Locations
Frame 10 or Frame 13 Power Structure
Use the AFE with PowerFlex
Drives
When the Active Front End is used with drives that have common mode
capacitors (for example, PowerFlex 7-Class or PowerFlex 750-Series drives),
the common mode capacitors of these drives
must be disconnected
. See the
documentation for the respective drives.
When supplying power to PowerFlex drives of different frame sizes on the same
DC bus, additional bus capacitance can be needed. For details, see Drives in
Common Bus Configurations, publication
Remove Three
Jumpers
Remove Three
Jumpers
Front View of LCL
Filter
IMPORTANT
The Frame 10 or Frame 13 AFE in an IP20 2500 MCC Style enclosure is
shipped from the factory with the common mode capacitors removed. You
do not need to remove the capacitors. However, when you replace a power
structure,
you must remove the common mode capacitors in the
new power structure
before installation. See
Frame 13 Power Structure on page 73
for instructions.
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......