Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
135
Troubleshooting
Chapter 5
Technical Support
When you contact technical support, be prepared to provide this information:
• Order number
• Product catalog number and drives series number (if applicable)
• Product serial number
• Firmware revision level (verify with parameter 033 [Control SW Ver])
• Most recent fault code
• Your application
The data that are contained in the following parameters helps in initial
troubleshooting of a faulted drive. Record the data provided for each listed
parameter in this table.
Parameter
Name
Description
Recorded Parameter Data
104
Fault Frequency
Captures and displays the AC line frequency at time of last fault.
105
Fault Total Curr
Captures and displays the DC bus amps at time of last fault.
106
Fault Bus Volts
Captures and displays the DC bus voltage at time of last fault.
107
Fault Temp
Captures and displays the heatsink temperature at time of last fault.
108
Status 1 @ Fault
Captures and displays [Cnvrtr Status 1] bit pattern at time of last fault.
109
Status 2 @ Fault
Captures and displays [Cnvrtr Status 2] bit pattern at time of last fault.
110
Alarm 1 @ Fault
Captures and displays [Cnvrtr Alarm 1] bit pattern at time of last fault.
111
Alarm 2 @ Fault
Captures and displays [Cnvrtr Alarm 2] bit pattern at time of last fault.
124
Fault 1 Code
Displays a code that represents the fault that tripped the AFE. The codes appear in these
parameters in the order they occur ([Fault 1 Code] equals the most recent fault).
126
Fault 2 Code
128
Fault 3 Code
130
Fault 4 Code
125
Fault 1 Time
Displays the time between initial unit power-up and the occurrence of the associated trip
fault. Can be compared to [Power Up Marker] for the time from the most recent power-up.
[Fault x Time] - [Power Up Marker] = Time difference to the most recent power-up. A
negative value indicates that fault occurred before most recent power-up. A positive value
indicates that fault occurred after most recent power-up. Time stamp of the fault occurrence.
127
Fault 2 Time
129
Fault 3 Time
131
Fault 4 Time
137…140
Alarm Code 1…4
Displays a code that represents a converter alarm. The codes appear in the order they occur
([Alarm 1 Code] = the most recent alarm). A time stamp is not available with alarms.
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......